  "affected": [
    {
      "database_specific": {
        "unresolved_ranges": [
          {
            "events": [
              {
                "introduced": "0"
              },
              {
                "last_affected": "9.0.2"
              }
            ]
          },
          {
            "events": [
              {
                "introduced": "0"
              },
              {
                "last_affected": "9.0.2"
              }
            ]
          }
        ]
      }
    }
  ],
  "details": "Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. The 'ShowDownload()' function uses “sprintf()” to format a string that includes the user-controlled input of 'GetParameter(meter)' in the fixed-size buffer 'acStack_4c' (64 bytes) without checking the length. An attacker can provide an excessively long value for the 'meter' parameter that exceeds the 64-byte buffer size.",
  "id": "CVE-2025-11782",
  "modified": "2026-03-10T21:49:00.124400931Z",
  "published": "2025-12-02T13:15:49.420Z",
  "references": [
    {
      "type": "ADVISORY",
      "url": "https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0"
    }
  ],
  "severity": [
    {
      "score": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
      "type": "CVSS_V3"
    }
  ]
}