Strobe Coverage Calculator Guide
The Strobe Coverage Calculator by System Sensor assists in designing audible/visible notification device circuits according to NFPA 72 standards. It calculates performance-based strobe coverage using the inverse square law and requires a minimum illumination of 0.0375 lumens/ft² within the covered area. Users are responsible for their product selections and System Sensor disclaims any ...

The document provides calculations for strobe coverage in a room, using two examples based on different angles and distances. It details how to determine effective candela and lumens per square foot to meet UL 1971 and NFPA 72 requirements. The calculations assume a square room and involve determining light intensity levels from a ceiling-mounted light source.
PDF AV Appliance Applications Guide

What About Photosensitive Epilepsy and Strobe Flash Rates? People who are vulnerable to photosensitive epilepsy have voiced con-cern over the cumulative effect of seeing multiple flashing strobes in the field of view. An example of this would be an individual standing at the cross-point of an "L" shaped corridor that contains multiple strobes .
Strobe Coverage Examples Following are two examples of the calculations used in determining the correct strobe coverage mearsurements. For both examples, the following variables are applied: Ceiling Height = 20 ft.

Tools & Software
System Sensor is pleased to provide this Strobe Coverage Calculator , formerly known as Equivalent Facilitation Calculator . The calculator was programmed to assist you in the design of audible/visible notification device circuits.
6 The NFPA is very specific with respect to strobe count and spacing using room size as the determining variable. Four different strobe count and spacing solutions are offered in conjunction with tables 7.5.4.3.1(a), 7.5.4.3.1(b) and figure 7.5.4.3.1 in this sec- tion of NFPA 72 2007: 1. Use a single visible notification appliance. 2.
PDF Strobe Application Guide
Our strobe Application Guide will help you to successfully apply EST strobes to your new construc-tion and renovation projects. This handbook provides a concise summary of basic guidelines normally followed when recommending strobe signals for fire alarm applications.
The Strobe Calculator intends to Satisfy provisions of the NFPA 72 and the UL 1971 for building room configurations not listed on the NFPA 72, 2010* Tables 18.5.4.3.1(a) and 18.5.4.3.1(b)

System Sensor Strobe Coverage Calculation Examples
Download System Sensor Strobe Coverage Calculation Examples PDF . Fire Alarm Resources has free fire alarm PDF manuals, documents, installation instructions, ...





Failure to use the proper units results in errors. For each of the three test sites, basic calculations were done using nominal ceiling heights and strobe spacings and the reported strobe intensities. Two simplified sets of calculations are presented. The first is for an imaginary square coverage area with the plane through the center of the wall.