Automated quantity takeoff · VLM Run

16 Tight Loop Drive

Nine sheets of issued construction documents, read end to end in under eight minutes. Every number on this page cites the spot on the drawing it came from: hover a row and the sheet pane finds it. Click to pin, Escape to release.

The set, with everything we found on it

The original PDF, rendered as vector so it stays sharp however far you zoom. Every one of the 2,833 detections across the nine sheets is drawn on top and colour-coded by what it is. Hover any box to see what was pulled out of it. Scroll to zoom, drag to pan, and use the pills to show or hide a class.

SheetShow

One box per line of lettering, plus the note panels and tables down the right-hand column, the titled drawings, the red field callouts with their leader lines and what each one marks, the pink hold-down dots, and the counted symbols. Title block text runs sideways on the sheet and is read in that orientation.

Trade quantities

Hover any row to see exactly where on the drawing the number came from. Click to pin it, Escape to release.

Division 03 · Concrete

Wall section, footing size and reinforcing are printed on A2.2. The perimeter they multiply is measured off the drawing.

ItemQuantityWhere it comes fromBasis
Foundation wall, 8″ × 4'-0″37.3 cy378 lf measured perimeter × section on A2.2Measured
Continuous footing, 16″ × 8″12.4 cySame perimeter, footing size from the sheet noteMeasured
Garage slab on grade, 4″16.0 cy1,292 sf from the FLOOR AREAS tableStated
Pier pads, 2'×2'×8″0.6 cy6 pads counted on A2.2Measured
14″ sonotubes6 eaCounted on A2.2Measured
#4 reinforcing, all locations2,898 lf0.97 tons at the spacings printed on A2.2Derived
Slab mesh, 6×6 W2.0×W2.01,292 sfOr #3 @ 18″ o.c. each way, contractor optionStated
Driveway, 4″ slab12.4 cy1,002 sf from the FLOOR AREAS tableStated
Patio and porch flatwork859 sf406 + 246 + 207 from the FLOOR AREAS tableStated
Structural concrete subtotal66.3 cyExcludes flatworkDerived

Division 06 · Wood and framing

Plate heights come from the elevation datums on A3.2, not from an assumption. Floor framing is 11-7/8″ LPI I-joists at 16″ o.c. per the callouts on A2.2.

ItemQuantityWhere it comes fromBasis
Exterior wall, 2×6 @ 16″ o.c.529 lf378 lf first floor + 151 lf second, both tracedMeasured
Interior partition, 2×4 @ 16″ o.c.315 lf250 lf first floor + 65 lf second, measured off the wall pocheMeasured
Exterior wall area at plate4,994 sfWeighted across the three plate heights on A3.2Derived
2×6 studs456 ea16″ o.c. plus 15% for corners and openingsDerived
2×4 studs272 ea16″ o.c. plus 15%Derived
Plate stock2,532 lf844 lf of wall, single bottom and double topDerived
Wall sheathing156 sheets4,994 sfDerived
Floor joists, 11-7/8″ LPI @ 16″ o.c.1,961 lfBay runs of 16', 34', 36', 39' and 60' called out on A2.2Derived
Second floor joists717 lf956 sf at 16″ o.c.Derived
Rim board378 lfFirst floor perimeterMeasured
Subfloor sheathing112 sheets3,570 sf both floorsDerived
Roof trusses @ 24″ o.c.78 eaPre-fabricated, 12″ energy heel per A2.3Estimated
Glulam, 5-1/8″ × 9″2 ea6'-3¼″ and 5'-6¾″, redlined on A2.3Redline
Glulam, 5-1/8″ × 15″1 eaPrinted on A2.3Measured
HDU5 hold-downs10 eaPink dots on A2.1, keyed beside the energy tableMeasured
Headers(2) 2×10 typ.3× 2×10 at the garage, per A2.3Stated

Division 07 · Thermal and moisture

No pitch triangle is printed anywhere on the set, so the slope was measured off the east elevation geometry. The set specifies two roofing systems, which is the single largest open item in this takeoff.

ItemQuantityWhere it comes fromBasis
Roof pitch8 : 12 475 roof edges on A3.2 agreeMeasured
Roof overhang2 ftStated on the A1.1 site planStated
Roof surface area6,355 sf5,288 sf projected × 1.2019 slope factorDerived
30 yr. asphalt shingles70 squaresIncludes 10% waste. See the split below.Estimated
Standing seam metal roofingsplit TBC A3.2 calls out both asphalt and pre-finished standing seam. Areas are not separated on the set.Redline
5/8″ OSB roof sheathing199 sheetsPer the A2.3 roof assembly noteDerived
Synthetic underlayment6,355 sfIce and water 2' in at eaves, 18″ each side of valleysDerived
1×8 fascia w/ 1×4 shadow board435 lfPainted Miratec, per A2.3Derived
Flat ceiling insulation, R-493,327 sfEnergy table, A2.1. Vaulted areas R-38.Stated
Above grade wall insulation, R-214,994 sfEnergy table, A2.1Derived
Crawl space, R-19 cavity / R-15 cont.2,614 sfEnergy table, A2.1Derived
Slab perimeter, R-10 for 4 ft378 lfEnergy table, A2.1Measured
Siding, gross5,629 sfHardiePlank lap at 5″ exposure, HardiePanel board and batten at 16″ o.c., plus 6″ stained vertical woodEstimated

Division 09 · Finishes

Drywall follows the measured wall runs and the measured plate heights. Flooring is the conditioned area from the title block.

ItemQuantityWhere it comes fromBasis
Drywall, walls9,663 sfPartitions both faces plus inside face of exteriorDerived
Drywall, ceilings3,327 sfConditioned areaStated
Drywall net of openings11,951 sf373 sheets 4×8, or 249 sheets 4×12Derived
5/8″ type X at garage2,352 sfGarage to dwelling separation, plan note 3 on A2.1Stated
Tape and finish1,793 lfJoints plus 20%Estimated
Flooring, conditioned3,327 sf1,951 sf first floor rooms, 641 sf second, balance circulationStated
Baseboard875 lfSum of room perimeters, garage and storage excludedDerived
Interior doors and hardware18 eaFrom the door scheduleMeasured

Division 26 · Electrical

Every device is matched against the symbol the ELECTRICAL LEGEND on E1.1 defines, so the count and the name come from the same source. Outlet variants are read from the label printed beside each one.

DeviceTotal1st2ndVariants read from labels
Duplex outlet876522Standard 50, GFI 17, Weatherproof GFI 10, GFI, 42" AFF 6, 220V 4
Recessed can light735914—
Pendant light761—
Smoke / CO detector743—
Ceiling fan321Standard 2, Redlined to chandelier 1
Surface mounted light220—

Legend coverage

Every row of the ELECTRICAL LEGEND on E1.1, and what the set actually contains. Where a symbol is counted, hover the row to light up every instance on the sheet. Where it is not, the row says so rather than guessing.

Legend symbolOn the plansNote
Recessed can light73
Duplex outlet8750 standard, 17 GFI, 10 weatherproof GFI, 6 GFI at 42″, 4 at 220V
Pendant light7
Smoke / CO detector7
Ceiling fan3one redlined on E1.1 to become a chandelier
Surface mounted light2
Wall mounted light—defined in the legend, not separately counted
Exhaust fan / fan-light—defined in the legend, not separately counted
Ceiling fan / light combination—counted within the ceiling fan family
Fluorescent light—defined in the legend, not separately counted
Wall switch, 3-way, 4-way, dimmer—defined in the legend, not separately counted

Rooms and surfaces

This is the layer estimating teams already work in: room by room, with the surfaces an estimator prices. Every room name was paired with the dimension string printed under it, so both cite the same spot on A2.1. Vertical surface is the room perimeter at its own measured ceiling height.

RoomFloorPrinted dimensionsFloor sfPerimeter lfVertical surface sf
Garage1st35-0 X 32-01,1201341,219
Living1st18-8 X 19-035575835
Kitchen1st18-8 X 15-628968621
Master Bedroom1st16-0 X 15-024062564
Dining1st13-4 X 13-417853485
Master Bath1st16-8 X 9-1016453482
Guest/ Office1st12-2 X 12-014648439
Storage1st5-8 X 19-010849448
Foyer1st12-2 X 8-410141373
Laundry1st10-6 X 9-610040364
Master Closet1st12-4 X 7-109740366
Mud Room1st9-0 X 8-07234309
Pantry1st10-2 X 7-07134312
Guest Bath1st10-0 X 5-05030273
Mechanical1st6-0 X 8-04828255
Shower1st11-4 X 4-04531279
Pwdr.1st6-0 X 6-03624218
Cl.1st5-0 x 5-02520182
W.C.1st7-4 X 3-02221188
Shwr.1st3-0 X 3-0912109
Flex2nd16-0 X 15-825163576
Bedroom 22nd13-0 X 11-014348437
Bedroom 32nd13-0 X 11-014348437
Bath32nd11-0 X 9-610441373
Labelled rooms3,9171,099

Labelled rooms total less than the gross floor areas because circulation and wall thickness are not labelled rooms. The title block states 2,496 sf and 831 sf gross.

Door schedule

Every opening on the plan carries a printed size callout. Heights of 80″ and 84″ are doors.

SizeCountType
30″ × 80″7
36″ × 80″6
32″ × 80″2
72″ × 80″2
84″ × 84″2Full Lite Slider
60″ × 80″1Tempered
9'-0"W x 9'-0"H1Overhead garage door
18'-0"W x 9'-0"H1Overhead garage door

Window schedule

Twenty units, 196 sf of glazing. Two 72″ × 60″ units are marked EGRESS at the second floor bedrooms and the plan notes call for tempered glazing at the sliders and the master bath.

SizeCountType
30″ × 48″6Single Hung
24″ × 48″4Singlehung
24″ × 24″3Tempered
60″ × 42″2Fixed
30″ × 42″2Single Hung
84″ × 24″2Fixed
72″ × 24″1Fixed

Stated areas

The architect's own FLOOR AREAS table, read as a table. Nothing in the measurement pass looked at these numbers.

AreaStated
1st floor2,496 sf gross
2nd floor831 sf gross
Total area3,327 sf gross
Garage / storage1,292 sf gross
Covered rear patio406 sf
Grilling patio246 sf
Covered front porch207 sf
Driveway1,002 sf
Total hardscape1,861 sf

Field markup

The set carries two layers of annotation that a plain text extraction walks straight past. Both are found by colour, then read, then tied to whatever the leader line points at.

Red callout and its leaderWhat the leader points atPink hold-down dot
Red callouts
16across 6 sheets
Revision clouds
3red, on A2.1 and A3.2
Hold-down dots
10HDU5, plus one key swatch
SheetWhat it saysWhat it points at
A2.1FIREPLACE FRAME OUT DIMENSIONS: - 49" W X 42 1/8" H - BOTTOM OF FP 14" FROM GROU“GAS FIREPLACE”
A2.13X LSL PACKOUT“EMPERED”
A2.2161-10 174“DOUBLE JOIST UNDER ISLAND”
A2.2DOUBLE JOIST UNDER ISLAND“34' LPI 11-7/8" I-JOISTS”
A2.3BOTTOM CHORD = 1 EACH 16' 8X8 D = 1 EACH 16'8X8 TOP CHORD= 2 EACH 18' 8X8 EACH 1—
A2.32 LAYER SHEETING 1ST LAYER- BRECKI 1ST LAYER- BRECKEN RIDGE—
A2.3BOTTOM CHORD= 1 EACH 16' 8X8 TOP CHORD= 2 EACH 16' 8X8“.S. TIRUSS”
A2.3USE 22' 8X10 RS BRACES= 1 EACH 8'6X6 BRACES= 1 EACH 8' 6X6—
A2.3USE 20' 8X10 RS“8X10 R.S. ROOF BEAM”
A2.36'-3 1/4ADER 6'-3 1W4ADER 31W4ADER 5 1/8 X 9'“HEADER”
A2.35'-6 3/4" GLULAM“HEADER”
A2.3TOP CHORD= 1 EACH 18' 8X8 BRACES= 1 EACH 10'6X6 BRACES= 1 EACH 10' 6X6“S 8 TTUS”
A2.3USE 24'8X10 RS USE 24' 8X10 RS—
A2.3TOP CHORD= 1 EACH 18' 8X8 BRACES= 1 EACH 10'6X6 BRACES= 1 EACH 10' 6X6—
A3.2Black Malarkey—
E1.1NO FAN. TO BE CHANDELIER“Ceiling fan”

Why these matter

  • Two roofing systems, not one. A3.2 calls out 30 yr. asphalt shingle roofing and pre-finished standing seam metal roofing, and a red note names the shingle as Black Malarkey. The set does not separate the areas, so the 70 square asphalt figure covers the whole roof until that split is confirmed.
  • The living room fan is not a fan. E1.1 carries a red callout reading NO FAN. TO BE CHANDELIER over the ceiling fan symbol. The symbol was never changed, so a count taken from symbols alone gets this wrong.
  • Timber truss members are redlined, not scheduled. A2.3 carries member lists in red: bottom chord 1 each 16' 8×8, top chord 2 each 18' 8×8, braces 1 each 10' 6×6, and 20', 22' and 24' 8×10 rough sawn. That is a lumber order living in field markup.
  • Ten HDU5 hold-downs. Drawn as pink dots on A2.1 and keyed beside the energy table. They are a hardware line item and a structural inspection item.
  • Fireplace frame-out is dimensioned in red. 49″ W × 42-1/8″ H, bottom of firebox 19″ from ground, 2×10 full-width blocking. None of that is in the black drawing.

Symbols found on the drawings

Counting repeated symbols is the slowest part of a manual takeoff and the part estimators most often get wrong. Every symbol below was located on its sheet and classified, then grouped by CSI division. Hover a row and every instance lights up on the sheet at once, in that symbol's own colour. Click to pin it.

Symbols located
322
Classes
27across 6 divisions
Sheets
A2.1 and E1.1floor plans and electrical

Floor plans, sheet A2.1

Post or columnDoor swingLavatoryWater closetStair runDouble doorRefrigeratorShowerWater heaterKitchen sinkBathtubFireplaceDryerWasherDishwasherRange / cooktop

Division 04 Masonry

SymbolCount1st2ndWhat it is
Fireplace110Gas fireplace, redlined with frame-out dimensions.
Total1

Division 06 Framing

SymbolCount1st2ndWhat it is
Post or column23230Solid post drawn inside a wall, or a hold-down marker.
Stair run211Tread run with a direction arrow.
Total25

Division 08 Openings

SymbolCount1st2ndWhat it is
Door swing17125Single leaf, counted from the swing arc drawn in the wall.
Double door220Two leaves swinging together, counted once, not twice.
Total19

Division 11 Appliances

SymbolCount1st2ndWhat it is
Refrigerator220Labelled REF. on the plan.
Dryer110Labelled D in the laundry.
Washer110Labelled W in the laundry.
Dishwasher110Labelled DW on the plan.
Range / cooktop110Burner symbol at the double wall oven.
Total6

Division 22 Plumbing

SymbolCount1st2ndWhat it is
Lavatory642Vanity basin symbol.
Water closet321Toilet symbol.
Shower220Shower pan, drawn as a square with a cross.
Water heater220Tank symbol in the mechanical room.
Kitchen sink220Double basin symbol in the island.
Bathtub211Tub symbol.
Total17

Electrical, sheet E1.1

The blue curves on E1.1 are wiring runs, not devices. Every class below is one the ELECTRICAL LEGEND on that sheet defines, so the count and the name come from the same place. Outlet variants are read from the label printed beside each device.

Duplex outletRecessed can lightWall switchSmoke / CO detectorFluorescent stripPendant lightWall mounted lightExhaust fanSurface mounted lightCeiling fanCeiling fan with light

Division 26 Electrical

SymbolCount1st2ndWhat it is
Duplex outlet765818Standard 42, GFI 16, Weatherproof GFI 9, GFI at 42″ 5, 220V 4
Recessed can light735914Square with a circle inside. Confirmed at 73 by a second, independent method.
Wall switch554510Letter S on a wall. Includes 3-way, 4-way and dimmer variants.
Smoke / CO detector1064Drawn as a stacked SD and CO pair.
Fluorescent strip10100Long thin rectangle. Each measures 4'-0″ at the sheet scale, in the garage.
Pendant light981Circle with a filled dot.
Wall mounted light752Half circle on a wall with a stem.
Exhaust fan642Circle with a filled comma. Bath and powder room ventilation.
Surface mounted light550Circle with rays.
Ceiling fan211Four blades. One is redlined on E1.1 to become a chandelier.
Ceiling fan with light110Four blades with a filled hub.
Total254

What this does not cover yet

Said plainly so the counts are not over-read.

  • Recessed cans agree at 73 from two independent methods. One matched the legend symbol across the sheet, the other located devices spatially. They never saw each other's output.
  • Wall switches are one class, not four. The legend separates plain, 3-way, 4-way and dimmer by the small superscript beside the S. Fifty-five covers all of them together.
  • One water closet is missed. Three found against four bathrooms with a toilet. Shown as found rather than adjusted to match.
  • Door swings include a few window openings. Seventeen singles plus two doubles against twenty in the printed schedule. Cross-check before ordering.
  • Posts and hold-downs are grouped. Twenty-three covers both the solid posts drawn in walls and the pink hold-down markers, which are separated on the Field markup tab.
  • Fluorescent strips were found by geometry, not by the detector. Ten of them, nine in a 3x3 grid over the garage and one in storage, every one measuring 4.02 ft at the sheet scale. A symbol with an exact, rigid signature is better found by measuring than by asking a model.
  • No home runs or circuits. Devices are counted; the wiring runs are not traced, and E1.1 itself says fixture, switch and outlet locations are all to be verified with the owner.

Every drawing on the set

Every viewport on the set is found by its own title marker and scale, then summarised. A summary is a reading aid, not a measurement: it lets you see what is on a sheet without opening it, and it is what surfaced the two overhead door sizes and the second roofing system. Anything that matters was then confirmed against the printed text. Click a card to bring it up in the sheet pane.

Viewports
17
Described by
Vision modelone call per viewport
Wall clock
116seconds, 8 at a time
Cover RenderingCover · NTS

An exterior elevation (axonometric-style) view of a single-story residential structure with multiple gable roof planes, a projecting two-story gable bay, a front covered porch, and an attached open carport. The view shows the building envelope only, with no visible title block, dimensions, scale, or material callout text.

What an estimator can take off this view (9)
  • gable roof planes - 4 principal gable roof forms drawn (left wing, central tower, porch roof, right wing) plus 1 small gable roof over the far-right entry
  • windows, left gable wall - 3 rectangular windows (center one adjacent to a small panel/vent detail)
  • windows, central two-story bay - 2 (one upper 4-pane, one lower 4-pane)
  • windows, right of porch - 1 wide two-unit window assembly
  • windows, right gable end - 1 small square window
  • windows, far right wall - 2 narrow vertical windows
Estimator note
  • No dimensions, scale, north arrow, title block, sheet number, or written material/schedule callouts are legible in this viewport, so no quantities can be priced from this view alone. No revision clouds, substitutions, or conflict notes are visible. Window/door counts are drawn elements only and must be verified against a window/door schedule and a dimensioned plan before takeoff.
Site PlanA1.1 · 1"=10'-0"

This is the SITE PLAN (scale 1" = 10'-0") for LOT 4 in Riverwood South Subdivision, showing the building footprint, property lines, setbacks, easements, a septic field, a well, and a concrete driveway off Tight Loop Drive. It also carries utility service "verify loc" markers and grading/landscaping/drainage notes.

CONCRETE DRIVEWAYSEPTIC FIELDWELLRIDGE VENT, TYP.HARDSCAPE (LOT 4 data block)PROPERTY LINE
What an estimator can take off this view (15)
  • LOT 4 lot area - 34,335 SF (0.788 ACRES)
  • Building footprint - 3,788 SF
  • Hardscape - 1,861 SF
  • Lot coverage - 16.5%
  • Front setback - 25'-0" (top and right)
  • Rear setback - 30'-0" (left)
Estimator note
  • Electrical, gas, water, and septic service tie-in points are marked only 'VERIFY LOC' with no firm coordinates or distances, so utility run lengths cannot be priced from this sheet. The septic field is outlined but no tank size, depth, or bed dimensions are printed. The well is shown with a 'WELL SPHERE OF INFLUENCE' circle but no depth/diameter. The note 'ALL ROOF OVERHANGS ARE 2 FT. UNLESS NOTED OTHERWISE' governs
2Nd Floor PlanA2.1 · 3/16" = 1'-0"

This is a 2nd floor plan viewport (sheet 2, scale 3/16" = 1'-0") showing Bedroom 2 (13-0 x 11-0) with its window and door openings dimensioned, plus a portion of an adjacent raked-wall space to the right. The right-hand edge of the drawing is cropped, so several callouts and overall dimensions are cut off mid-text.

RAKED WALLGUARDRAILWALLFIREPL[ace] (red note, truncated)2x10 F[raming] (red note, truncated)
What an estimator can take off this view (27)
  • Window/door - 69"X36" FIXED (7'-9" HEAD)
  • Window/door - 60"X42" FIXED (7'-6" HEAD)
  • Window/door - 72"X48" SINGLE SWING EGREASS (7'-6" HEAD)
  • Opening (green text) - 72"X80"
  • Opening (green text) - 32"X80"
  • Room label - BEDROOM 2
Estimator note
  • Right edge of viewport is cropped: overall widths (43'-8", 16'-8", 9'-11") and the adjacent room label (FLEX..., 16-0 X...) plus its dimensioning are incomplete and must be taken from the full sheet. A red note block at lower right (FIREPL..., - 49"W, - BOTTO..., - 2x10 F..., STARTI...) is truncated and likely specifies a fireplace opening / header / framing — confirm on full sheet. Window/door text reads 'EGREASS' (
1St Floor PlanA2.1 · 3/16" = 1'-0"

First floor plan (3/16" = 1'-0") of a residential house showing a two-car garage, storage, mechanical, mud room, laundry, kitchen, dining, living, foyer, guest/office, guest bath, master bedroom suite with master bath and master closet, Bedroom 3, Bath 3, plus concrete patios and a covered concrete porch. The sheet is heavily dimensioned with room sizes, door/window schedules, and structural notes (posts, LSL members).

CONCRETE GRILLING PATIOCOVERED CONCRETE PATIOCOVERED CONCRETE PORCHVAULTED CLG.11' CLG.9' CLG.
What an estimator can take off this view (30)
  • Overhead garage door - '9'-0"W x 9'-0"H OVERHEAD DOOR'
  • Overhead garage door - '18'-0"W x 9'-0"H OVERHEAD DOOR'
  • Garage single hung window - '30" X 48" SINGLE HUNG (7'-6") HEAD' (x4 shown along garage walls)
  • Storage single hung - '30" X 48" SINGLE HUNG (7'-6") HEAD'
  • Concrete grilling patio - '13-4 X 18-0'
  • Covered concrete patio - '20-4 X 19-0'
Estimator note
  • Red revision callout '3X LSL PACKOUT' with two red circles tying into the covered porch header area. Red note at left (partially cut off) references 'FACE FRAME OUT DIMENSIONS', 'X 42 1/8" H', 'OM OF FP 14" FROM GROUND', 'ULL WIDTH BLOCKING', 'NG AT 65°'. 'NOTE: T.O.S. MIN. 9' DOWN FROM T.O.W. AT GARAGE DOORS' printed in garage. 'NOTE: GARAGE WALLS TO BE 10' WALLS' printed in garage. 'GAS REPLACE' circled in red near
FoundationA2.2 · 3/16"= 1'-0"

Foundation plan (scale 3/16" = 1'-0") of a single-story residence showing 4-ft concrete foundation walls, 16" wide concrete footings, perimeter and interior I-joist framing, pony walls, and a 4" concrete slab on garage/utility portion. A red review annotation 'DOUBLE JOIST UNDER ISLAND' points to an interior 34 LIP I-joist line near the kitchen island area.

4' FOOT WALL: 8" CONCRETE WALL W/ #4 VERTICAL BARS @ 116" W FOOTING W/ (3) #4 CONTINUOUS BARS - TYP4" CONCRETE SLAB W/ #3 BARS @ 18" O.C. EA. WAY 5/8 W2011-7/8" T A 12 WOOD I-JOISTS @ 16" O.C.16 LIP 11-7/8" I-JOISTS @ 16" O.C.28 LIP 11-7/8" I-JOISTS @ 16" O.C.
What an estimator can take off this view (13)
  • Foundation wall height - 4' FOOT WALL (printed in two wall callout blocks)
  • Concrete wall thickness - 8" CONCRETE WALL
  • Wall vertical rebar - #4 VERTICAL BARS @ 18" o.c.
  • Wall horizontal rebar - (3) #4 BARS HORZ @ 12" o.c.
  • Footing width - 16" W FOOTING W/ (3) #4 CONTINUOUS BARS
  • Pony wall footing - 16"X8" CONCRETE FOOTING W/ (2) #4 CONTINUOUS BARS
Estimator note
  • Red handwritten review mark 'DOUBLE JOIST UNDER ISLAND' points to the 34 LIP 11-7/8" I-JOIST line near the kitchen island, indicating a double/oversized joist condition not captured in the printed joist schedule - verify and price accordingly. Left NOTE block states all structural calculations are the builder's responsibility and foundation walls/footings must be verified by a geotechnical engineer; NOTE 'LATERAL ENG
Upper Floor FramingA2.3 · 3/16" = 1'-0"

Upper‑floor framing plan (sheet 1, scale 3/16" = 1'-0") showing the garage/upper structure with header lines, LVL and glulam floor beams, I‑joist spans, roof beams, timber trusses and red markup callouts. A north arrow and the title "UPPER FLOOR FRAMING" are printed at the bottom.

2X6 BEARING WALL2X LEDGER2X 11 7/8 LVL FLOOR BEAM8X10.5 ROOF BEAM16' LPI 111 7/8" I-JOISTS @ 16" O.C.18' LPI 111 7/8" I-JOISTS @ 16" O.C.
What an estimator can take off this view (17)
  • 8X8 R.S. TIMBER TRUSS - 3 instances labeled (vertical members over the opening)
  • 8X8 POST - 3 instances labeled (left, center, lower-left)
  • 3X 2X10 HEADER - 2 instances labeled
  • 2X6 BEARING WALL - 4 instances labeled
  • I-joist spans - 3 printed lengths: 16' / 18' / 26' LPI 111 7/8" @ 16" O.C.
  • Glulam header - 2 printed: 6'-3 1/8" 5 1/8 X 9" and 5'-6 3/4" 5 1/8 X 9"
Estimator note
  • Red clouded callouts (revision/markup) override the base framing: roof beams changed to "USE 22' 8X10 RS" and "USE 20' 8X10 RS"; timber‑truss chords and 6X6 braces specified by length with "CUT TO MATCH RENDERING" — confirm against the structural set and the rendering before pricing. Two different top‑chord lengths are printed for the two openings (18' 8X8 vs 16' 8X8); do not average them. "NOTE: GARAGE WALLS TO BE 1
Wall Section - 2-Story Dropped JoistsA2.3 · 3/4" = 1'-0"

A full-height exterior wall section through a two-story dropped-joist residence, drawn at 3/4" = 1'-0", showing the roof-to-footing build-up (shingles, trusses, shear walls, rim boards, subfloors, concrete stem wall and footing) with stacked typical floor elevations and egress-window clear-opening notes. The right-side legend lists the materials/assemblies at each layer while the left side carries the story-to-story dimension strings (9'-1 1/8", 7'-0", 1'-7 1/8", 3'-6", etc.).

30 YR. ASPHALT SHINGLES over SYNTHETIC ROOFING UNDERLA5/8" OSB over ENGINEERED WOOD TRUSSES w/ PROVIDE I/E &SPRAY FOAM URETHANE INSULATION AT EAVES2X BLOCKING EA. TRUSS BAY, HOLD DOWN 2" FOR ATTIC VENTPRE-FINISHED METAL DRI1X8 PIRATED MIRATEE FA SHADOW BOARD, TYP.
What an estimator can take off this view (19)
  • Sheet scale - 3/4"= 1'-0" (title block: WALL SECTION - 2-STORY DROPPED JOISTS)
  • Story height dim string - 9'-1 1/8" (T.O.B.O. 7'-6" TYPICAL 2ND FLOOR, CEILING U.N.O.)
  • Clear opening dim - 7'-0" (COMBINED CLEAR OPENING OF EGRESS WINDOWS 44" MIN. MAX.)
  • Story height dim string - 9'-1 1/8" (T.O.B.O. 7'-6" TYPICAL 1ST FLOOR HEAD HEIGHT U.N.O., 44 MAX. EGRESS WINDOWS)
  • Rim/head dim - 1'-7 1/8"
  • Stem wall height dim - 3'-6"
Estimator note
  • Several right-edge callouts are truncated in this viewport (e.g. 'PRE-FINISHED METAL DRI', '1X8 PIRATED MIRATEE FA', 'PRE-FINISHED VENTED FIBER-CEME', 'BITUMINOUS DAMPPROOFING TO GRA', 'VERTICAL #4 BARS SHALL HAVE A STAR', '16'x6" CONC. FOOTING W/ (2) #4 CONTS'); full text must be confirmed on the complete sheet before pricing. Window openings are not dimensioned here — 'WINDOW, SEE PLANS & ELEVATION(S) FOR SIZE & TY
3D View 1A3.1 · NTS

Exterior architectural line rendering of a two-story residential building showing a two-car garage wing on the left, a primary front-gabled living volume, a taller central massing, a covered front porch, and a projecting gable entry vestibule on the right with multiple windows. The viewport contains only the building geometry and shading; there are no dimension strings, text labels, legend, title block, or takeoff schedules printed on it.

What an estimator can take off this view (4)
  • double-hung / multi-pane windows - 7 visible (3 across the front gable wall, 1 small upper + 1 tall upper + 1 four-pane lower on the central volume, 1 on the right entry wall); no sizes, no
  • residential overhead garage doors - 2 visible on the recessed garage wall; no header/sill heights or door size printed
  • exterior eave light fixtures (lantern style) - 3 visible hanging under the left eave; no fixture spec or count schedule printed
  • porch / entry structural posts and beams - visible (2 front porch posts, 2 visible entry vestibule posts with rafter-tie beam); no post sizes or counts scheduled
Estimator note
  • No dimensions, levels, material callouts, window/door schedule, or title block are legible in this viewport, so no firm quantities or material assemblies can be priced from it alone. Surface treatments are depicted but not labeled: the left and central-lower walls are drawn with horizontal lap-siding lines, the central upper volume with vertical board-and-batten lines, and some gable ends with a shingle-like pattern
3D View 2A3.1 · NTS

This viewport is a perspective (3D) rendering of a large single‑family residential building showing multiple gabled roof volumes, an entry porch on the left, a tall two‑story central block, and an attached garage wing on the right. No title block, scale, north arrow, dimensions, room labels, or notes are present on the sheet—only the modeled building and a gradient sky background are drawn.

What an estimator can take off this view (8)
  • gabled roof planes (drawn) - 6 visible roof volumes (left entry wing, central steep gable, rear central gable, right front gable, right rear gable, plus porch gable)
  • windows (drawn, unlabeled) - 9 visible: 1 small window on left gable end, 1 window right of porch door, 1 large 4‑pane window upper on central block, 2 smaller windows lower on central block
  • exterior doors (drawn, unlabeled) - 1 main entry door under the left porch
  • garage door opening(s) (drawn, unlabeled) - 1 wide garage door on the far‑right elevation
  • porch support columns/posts (drawn) - 2 visible vertical posts at the left entry porch
  • roof‑bracket / corbel decorations (drawn) - multiple at eaves of each gable
Estimator note
  • No dimensions, scale, grid lines, section/level markers, or area takeoff data are printed in this viewport, so no lengths, areas, or elevations can be measured from it; it is a presentation‑only 3D render and cannot be used for quantity takeoff on its own. No revision clouds, substitutions, schedule tags, or material/assembly callouts are present, so no materials or assemblies are named verbatim. Window/door counts a
3D View 3A3.1 · NTS

This is a shaded 3D perspective (rendering) of a two‑story residential house showing the front elevation with a covered entry porch, multiple gabled roof planes, and several windows. It is a visual representation only — no dimensions, scales, title block, or text callouts are printed on the image.

What an estimator can take off this view (10)
  • window openings - none dimensioned or labeled; 1 single window on the left single‑story wing
  • window openings - none dimensioned or labeled; 1 wide double‑light window at the left of the covered porch
  • window openings - none dimensioned or labeled; sidelight(s) flanking the porch entry door
  • window openings - none dimensioned or labeled; 1 large double‑light window on the upper level of the central front gable
  • window openings - none dimensioned or labeled; 1 small window upper right of the central gable
  • window openings - none dimensioned or labeled; 2 small windows on the lower level of the central front gable
Estimator note
  • No scale, no dimensions, no grid coordinates, no title block, no legend, and no material/finishes schedule are present in this viewport, so no linear, area, or unit takeoff can be performed from this image alone. The image is an architectural rendering (shaded perspective), not a dimensioned construction sheet; any quantities listed above are visual counts only and must be confirmed against the actual elevations/sect
3D View 4A3.1 · NTS

This image is a shaded 3D perspective/rendering elevation of a single-family residence showing a one-story left wing, a two-story central mass with a front porch and entry, a recessed garage, and a one-story right wing with a small projecting bay. No scale bar, title block, dimension strings, or material legends are printed on the image.

What an estimator can take off this view (8)
  • exterior windows (left wing, lower level) - 3 visible rectangular windows, plus 1 square louvered vent between the first two
  • exterior windows (central two-story mass) - 1 double-hung type window on upper level, 1 double-hung type window on lower level
  • exterior windows (right wing) - 1 large multi-light window on the front face, 1 small square window, and 1 small multi-light window on the angled projecting bay
  • exterior doors (entry) - 1 double glass entry door in the porch, plus 1 wide glass door/panel unit to its right
  • garage door - 1 large sectional-style garage door on the recessed garage face, with 1 narrow pedestrian-style panel to its left
  • roof planes - 5 visible roof planes (left gable, rear/upper shed, central front gable/porch gable, right gable, and small right-bay gable)
Estimator note
  • No dimensions, no scale, no grid lines, no title block, no sheet number, and no material/assembly legends are printed anywhere in this viewport, so no linear or square takeoff can be taken directly from it. No revision bubbles, substitution notes, or conflict flags are visible. The image is a perspective rendering rather than a measured construction elevation; an estimator should rely on the corresponding plan/sectio
NorthA3.2 · 1/4" = 1'-0"

A north exterior elevation (scale 1/4" = 1'-0") of a two-story modern residence showing a two-car garage bay, an entry door with sidelights, a columned carport/open bay at left, and stacked upper-level massing with a parapet/roofline. A vertical stack of elevation (datum) marks is printed along the right edge.

What an estimator can take off this view (6)
  • Garage door openings - two (two-car garage, each with multi-pane sectional door drawn)
  • Entry door - one (paneled exterior door with transitory/overhead fixture drawn above)
  • Carport/support columns - four (two pairs framing the open left bay)
  • Elevation datum marks (printed) - 7: T.O. UPPER WALL 119'-2 7/8"; T.O. WALL LIVING RM 111'-1 1/8"; UPPER LEVEL 110'-1 3/4"; T.O. GARAGE WALL 110'-1 1/8"; T.O. WALL 109'-1 1/8"; MAIN LEVEL 10
  • Scale notation - 1/4" = 1'-0"
  • Direction indicator - NORTH+ with circled sheet number 2
Estimator note
  • No horizontal dimensioning (lengths/widths) is printed on this view—only vertical elevation datums—so width/area takeoff must come from the plan or other elevations. No material/finish schedule text is printed on this sheet; finishes and assembly types (cladding, garage door type, glazing) must be confirmed on other sheets/specs. Confirm whether the left open bay is a covered carport or enclosed space, as this drives
EastA3.2 · 1/4" = 1'-0"

Architectural EAST elevation of a multi-gabled residential front with porch, showing roofing, siding, window/door openings, and a stack of top-of-wall / level elevation heights on the right. A 1/4" = 1'-0" scale bar and sheet bubble "1" are at the lower left, with red field annotations ("Black Malarkey", "Black") clouded over two roof/wall areas.

30 YR. ASPHALT SHINGLE ROOFING, TYP.6" VERTICAL WOOD SIDING, STAINED, TYP.WOOD PORCH POSTS, BEAMS & BRACES, STAINED, TYP.TIMBER TRUSSES, STAINED, TYP.TIMBER BOX BRACES, STAINED, TYP.PRE-FASHED STANDING SEAM METAL ROOFING, TYP.
What an estimator can take off this view (6)
  • Window openings - 9 counted in this elevation (left small, porch large 4-pane, small right of porch, center-gable large 4-pane, center-right upper, right-gable left, right mid, right lower,
  • Glazed entry/porch door opening - 1 (double glazed door) at porch; spec printed as '1-1/4" DOORS & WINDOW TRIM, PAINTED, TYP.'
  • Exterior light fixtures - 'DARK SKY COMPLIANT EXTERIOR LIGHT FIXTURES, TYP.' (no count printed; one symbol shown at right)
  • Gable/ridge roof peaks - 4 major peaks visible (left flat-roof mass, center tall gable, right gable, porch gable)
  • Top-of-wall / level elevations (right side) - T.O. UPPER WALL 115'-2 7/8"; T.O. WALL, LIVING RM. 111'-1 1/8"; UPPER LEVEL 102'-1 3/4"; T.O. GARAGE WALL 110'-1 1/8"; T.O. WALL 109'-1 1/8"; MA
  • Roof rise dimensions at peaks - '8"' and '12"' printed at two gable peaks (pitch callouts)
Estimator note
  • Two red field/cloud annotations ('Black Malarkey' over left roof area, 'Black' over right upper-wall area) appear to be revision/color notes — Malarkey is a shingle brand, so this likely overrides the printed '30 YR. ASPHALT SHINGLE ROOFING, TYP.' for that zone; confirm intent with architect. Two different roof systems are called on one building (asphalt shingle vs. standing-seam metal), and three different wall syst
SouthA3.3 · 1/4"=1'-0"

South elevation/section of a single‑family residence showing a primary gable roof over a flat‑roofed right‑hand wing, a projecting entry/gable gable with three windows, a horizontal window in the left wall, and open porch supports at both ends. Vertical elevation markers are tabulated along the right edge from foundation top to roof‑line walls.

WALL (referenced in elevation tags: T.O. WALL. PM., T.FDN. WALL (referenced: T.O. FDN. WALL)
What an estimator can take off this view (12)
  • window - one horizontal (landscape) window on the left wall face
  • window - three small square/vertical windows in the projecting entry gable
  • window - 4 total window openings drawn in this elevation
  • roof pitch - primary gable roof marked with rise notation 12"
  • roof pitch - projecting entry gable marked with rise notation 5"
  • elevation marker - T.O. WALL. PM. = 119'-2 7/8"
Estimator note
  • Top horizontal/vertical dimension strings are present as leader lines and tick marks but carry NO legible numeric values, so overall building length, roof overhang, and wall heights cannot be taken off from this view alone – verify against plan/section sheets. Roof pitches are annotated only as 12" and 5" (rise figures); the run basis is not printed, so confirm 12:12 vs. 5:12 interpretation before roofing quantity ta
WestA3.3 · 1/4"= 1'-0"

This is a west elevation of a single‑family residence showing a two‑story main volume with a tall central gable, a single‑story side wing with a gable roof, and an attached two‑bay garage with gable roofs. It carries vertical dimension strings for wall tops, levels, and foundation top, plus roof‑pitch notes at each gable.

What an estimator can take off this view (14)
  • Window units (elevation) - 7
  • Garage overhead door openings - 2
  • Gable roof peaks - 4
  • Roof pitch (left wing gable) - 12" P
  • Roof pitch (central tall gable) - 12" P
  • Roof pitch (right gable) - 12" P
Estimator note
  • No wall cladding, trim, or finish materials are labeled in this viewport, so siding/soffit/fascia takeoff must come from other sheets or specs. Window and door sizes/quantities are not dimensioned here; only graphical sizes are shown. Overall building width and individual bay widths are not dimensioned in this viewport. A marker "2" appears at the lower left (possible revision/sheet callout) that should be reconciled
Electrical - 2Nd FloorE1.1 · 3/16" = 1'-0"

Second-floor electrical plan showing device layout (lights, switches, GFI outlets, a ceiling fan) across a central living area, two side bedrooms, a hall/stair opening marked 'DOWN', and two baths. The sheet is titled 'ELECTRICAL - 2ND FLOOR' at a scale of 3/16" = 1'-0".

ELECTRICAL - 2ND FLOOR3/16" = 1'-0"GFISDCODOWN
What an estimator can take off this view (9)
  • ceiling fan symbol - 1 drawn in central room
  • GFI-labeled outlets - 2 (top-center room, left and right)
  • SD-labeled switches - 3 (left bedroom, center hall, right bedroom)
  • CO alarm label - 1 (center, below an SD)
  • 'DOWN' stair/opening arrow - 1 (top-center room)
  • bed symbols - 3 (one per bedroom/room with headboard)
Estimator note
  • Red revision note reads 'NO FAN. TO BE CHANDE...' (text cut off at right edge, likely 'CHANDELIER'), which removes the drawn ceiling fan and substitutes a chandelier in that room — a direct price change. Top-right general notes are partially clipped: one cites backup-power requirement per 'SECTION R314.6 & R315.6' and item 9 cites 'CARBON MONOXIDE ALARMS ... VICINITY OF BEDROOMS ... SECTION R315.3'; full text is not
Electrical - 1St FloorE1.1 · 3/16" = 1'-0"

First-floor electrical plan showing wiring runs (blue), receptacles (GFI, 220V, SD, CO), ceiling fixtures (CLG.), ceiling fans, and equipment locations for a residence with a garage, kitchen island, and multiple bedrooms/baths. A carbon-monoxide installation notes block and a partially cut title block appear at the left/bottom edges.

AC UNITELECTRICAL PANELUNDER CABINET LIGHTINGDWG.D.WH
What an estimator can take off this view (15)
  • Electrical panel - 'ELECTRICAL PANEL'
  • Meter - 'ELECTRICAL METER VERIFY LOC.'
  • AC unit - 'AC UNIT'
  • Ceiling fixtures - 'CLG.'
  • GFI receptacles - 'GFI' (multiple symbols)
  • GFI weatherproof receptacles - 'GFI WP' (exterior symbols)
Estimator note
  • Left-edge notes are truncated: a carbon-monoxide ('...ONE NOTES:') block citing section numbers (e.g. R314.3, R314.1, R315.2) and an owner-coordination box ('...ONS WITH OWNER') are cut off, so full CO/owner requirements cannot be taken off from this sheet. Meter location is flagged 'VERIFY LOC.' and is therefore unconfirmed. A red-highlighted ceiling fan symbol in the living room suggests a markup/revision. Dashed-l

The set as text

Every written panel on the set, read back in the shape it was drawn in. Notes come back as headed, numbered prose. Tables come back as rows and cells, which is what lets the stated areas be checked against what we measured. Click a panel to bring it up in the pane.

Lines read
2,016text lines across 9 sheets
Note panels
7read as prose
Tables
4read as rows and cells
General NotesA1.1

Read as prose · 561 characters

# GENERAL NOTES

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB SITE CONDITIONS BEFORE COMMENCING WORK AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. GENERAL CONTRACTOR TO COORDINATE ARCHITECTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING.

## APPLICABLE CODES:

* 2018 INTERNATIONAL RESIDENTIAL CODE

* 2018 UNIFORM PLUMBING CODE

* 2018 INTERNATIONAL MECHANICAL CODE

* 2017 NATIONAL ELECTRIC CODE

* 2018 INTERNATIONAL FUEL GAS CODE

* 2018 INTERNATIONAL ENERGY CONSERVATION CODE

## DESIGN CRITERIA

* SEISMIC ZONE D0

* 115 MPH WIND

General NotesA2.1

Read as prose · 553 characters

# GENERAL NOTES

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB SITE CONDITIONS BEFORE COMMENCING WORK AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. GENERAL CONTRACTOR TO COORDINATE ARCHITECTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING.

## APPLICABLE CODES:

- 2018 INTERNATIONAL RESIDENTIAL CODE
- 2018 UNIFORM PLUMBING CODE
- 2018 INTERNATIONAL MECHANICAL CODE
- 2017 NATIONAL ELECTRIC CODE
- 2018 INTERNATIONAL FUEL GAS CODE
- 2018 INTERNATIONAL ENERGY CONSERVATION CODE

## DESIGN CRITERIA

- SEISMIC ZONE D0
- 115 MPH WIND
Plan NotesA2.1

Read as prose · 2,036 characters

# PLAN NOTES

## FIRE RESISTANT CONSTRUCTION REQUIREMENTS

1. DOOR(S) BETWEEN GARAGE & HOUSE SHALL BE 20-MINUTE & EQUIPPED WITH A SELF-CLOSING DEVICE.

2. INSTALL 1/2" GWB @ WALLS & UNDER-STAIR SURFACE IN ENCLOSED ACCESSIBLE SPACE UNDER STAIRS

3. **1/2" GWB SHALL BE INSTALLED ON ALL WALLS SEPARATING THE GARAGE FROM THE DWELLING.**

4. WHERE HABITABLE ROOMS ARE ABOVE A GARAGE, APPLY 5/8" TYPE 'X' GWB ON GARAGE CEILING & 1/2" GWB ON WALLS SUPPORTING FLOOR ABOVE

5. FOAM INSULATION SHALL BE SEPARATED FROM THE INTERIOR OF A BUILDING BY AN APPROVED THERMAL BARRIER OF MINIMUM 1/2 INCH GWB OR A MATERIAL THAT IS TESTED IN ACCORDANCE NFPA 275.

6. PROVIDE FIRE BLOCKING VERTICALLY AT THE CEILING AND FLOOR LEVELS & HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

7. FLAME SPREAD FOR WALLS AND CIELINGS FINISHED TO BE NOT GREATER THAN 200. PER (R302.92)

8. THE SMOKE-DEVELOPED INDEX FOR WALLS AND CIELINGS SHALL NOT HAVE AN INDEX GREATER THAN 450. PER (R302.92)

## EMERGENCY ESCAPE AND RESCUE OPENINGS (EEROs)

ALL SLEEPING ROOMS SHALL HAVE AN EMERGENCY ESCAPE AND RESCUE OPENING (EEROs) OPPENING DIRECTLY TO THE OUTSIDE VIA A DOOR OR WINDOW. EGRESS WINDOWS SHALL MEET THE REQUIREMENTS OF IRC 2018 SECTION R310.1

## MECHANICAL

1. CONTRACTOR TO CONFIRM SIZE & TYPE OF WATER HEATER, SET HEATER IN 1 1/2" DEEP 24 GA. GALVANIZED STEEL PAN DRAINED w/ 3/4" INDIRECT WASTE PIPE. WATER HEATERS SHALL BE ANCHORED OR STRAPPED TO PREVENT HORIZONTAL MOVEMENT

2. ELEVATE WATER HEATER 18" MINIMUM ABOVE GARAGE SLAB TO ANY ELEMENT OR SWITCH THAT MAY SPARK

3. A PERMANENT CRAWL SPACE LADDER OR ATTIC SPACE PULL DOWN LADDER IS TO BE INSTALLED TO ACCESS THE HEATING UNIT OR BOILER.

4. THE MAXIMUM CLEAR TRAVEL PATH FROM THE CRAWL SPACE OR ATTIC ACCESS OPENING TO THE HEATING UNIT OR BOILER IS 20 FEET.

5. PROVIDE LIGHT FIXTURE CONTROLLED BY A SWITCH LOCATED AT THE CRAWL SPACE ACCESS HATCH & A RECEPTACLE OUTLET SHALL BE INSTALLED AT OR NEAR THE FURNACE.

## SAFETY GLAZING REQUIREMENTS

1. TEMPER GLAZING AT LOCATIONS SPECIFIED IN IRC 2018 R308.4
Energy RequirementsA2.1

Read as a table · 889 characters

ENERGY REQUIREMENTS
2018 INTERNATIONAL ENERGY CONSERVATION CODE
MONTANA CLIMATE ZONE 6B
INSULATION & FENESTRATION REQUIREMENTS BY COMPONENT
CEILING FLAT:FLATR-49
VAULTEDR-38
WALLS:ABOVE GRADER-21
BASEMENTSR-19 CAVITY/ R-15 CONT.
CRAWL SPACER-19 CAVITY/ R-15 CONT.
FLOORS:OVER UNHEATED SPACESR-30
PERIMETER SLAB FOR 4 FT.R-10
EXTERIOR DOORSR-3
WINDOWSNFRC UNIT RATINGU-0.30
WATER HEATERENERGY FACTOR RATING0.58
HEATING SYSTEMENERGY EFFICIENCY RATING 78% (AFUE FOR GAS; HSPF HEAT PUMP)
Floor AreasA2.1

Read as a table · 440 characters

FLOOR AREAS
1ST FLOOR:2,496SF GROSS
2ND FLOOR:831SF GROSS
TOTAL AREA:3,327SF GROSS
GARAGE/STORAGE:1,292SF GROSS
COVERED REAR PATIO:406SF
GRILLING PATIO:246SF
COVERED FRONT PORCH:207SF
DRIVEWAY:1,002SF
TOTAL HARDscape Area:1,861SF
General NotesA2.2

Read as prose · 545 characters

# GENERAL NOTES

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB SITE CONDITIONS BEFORE COMMENCING WORK AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. GENERAL CONTRACTOR TO COORDINATE ARCHITECTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING.

**APPLICABLE CODES:**

2018 INTERNATIONAL RESIDENTIAL CODE

2018 UNIFORM PLUMBING CODE

2018 INTERNATIONAL MECHANICAL CODE

2017 NATIONAL ELECTRIC CODE

2018 INTERNATIONAL FUEL GAS CODE

2018 INTERNATIONAL ENERGY CONSERVATION CODE

**DESIGN CRITERIA**

SEISMIC ZONE D0

115 MPH WIND
Energy RequirementsA2.2

Read as a table · 820 characters

ENERGY REQUIREMENTS
2018 INTERNATIONAL ENERGY CONSERVATION CODE MONTANA CLIMATE ZONE 6B
INSULATION & FENESTRATION REQUIREMENTS BY COMPONENT
CEILING FLAT:FLATR-49
WAALLS:VAULTEDR-38
FLOORS:ABOVE GRADER-21
EXTERIOR DOORS WINDOWSBASEMENTSR-21 CAVITY/ R-15 CONT.
WATER HEATER HEATING SYSTEMCRAWL SPACE OVER UNHEATED SPACESR-19 CAVITY/ R-15 CONT. R-30
R-10 U-0.30PERIMETER SLAB FOR 4 FT.R-3
RETI আগed, O为宜PERIMETER SLAB FOR 4 FT. U-0.30R-3 U-0.30
ENERGY FACTOR RATING ENERGY EFFICIENCY RATING (AFUE FOR GAS, I SPH F销售)ENERGY FACTOR RATING ENERGY EFFICIENCY RATING RATING (AFUE FOR GAS, I SP F销售)0.58
General NotesA2.3

Read as prose · 779 characters

# GENERAL NOTES

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB SITE CONDITIONS BEFORE COMMENCING WORK AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. GENERAL CONTRACTOR TO COORDINATE ARCHITECTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING.

## APPLICABLE CODES:

* 2018 INTERNATIONAL RESIDENTIAL CODE

* 2018 UNIFORM PLUMBING CODE

* 2018 INTERNATIONAL MECHANICAL CODE

* 2017 NATIONAL ELECTRIC CODE

* 2018 INTERNATIONAL FUEL GAS CODE

* 2018 INTERNATIONAL ENERGY CONSERVATION CODE

## DESIGN CRITERIA

* SEISMIC ZONE D0

* 115 MPH WIND

> "BEFORE TOP Dropped, The connections to be 1/2" lag
> "Dropped" from top to bottom, The bottom
> "down" to bottom up must be 1/2" lag
> "under" to be 1/2" lag
> "sunk" to be 1/2" lag

> "8' 8X8(USE CUTOFF FOR KINGS)"
General NotesE1.1

Read as prose · 561 characters

# GENERAL NOTES

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB SITE CONDITIONS BEFORE COMMENCING WORK AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT.

2. GENERAL CONTRACTOR TO COORDINATE ARCHITECTURAL DRAWINGS WITH MECHANICAL, ELECTRICAL, AND PLUMBING.

**APPLICABLE CODES:**

* 2018 INTERNATIONAL RESIDENTIAL CODE

* 2018 UNIFORM PLUMBING CODE

* 2018 INTERNATIONAL MECHANICAL CODE

* 2017 NATIONAL ELECTRIC CODE

* 2018 INTERNATIONAL FUEL GAS CODE

* 2018 INTERNATIONAL ENERGY CONSERVATION CODE

**DESIGN CRITERIA**

* SEISMIC ZONE D0

* 115 MPH WIND
Electrical NotesE1.1

Read as prose · 3,197 characters

# ELECTRICAL NOTES

A. ALL OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY ROOMS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE **ARC-FAULT CIRCUIT INTERRUPTER** INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.

B. IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN, SUN ROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH THESE PROVISIONS:

1. RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET, FROM A RECEPTACLE OUTLET.

2. A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP SPACE 12 INCHES OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 INCHES, MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.

3. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 24 INCHES OR GREATER AND A SHORT DIMENSION OF 12 INCHES OR GREATER.

4. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION OF 24 INCHES OR GREATER AND A SHORT DIMENSION OF 12 INCHES OR GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTING EDGE.

5. AT LEAST ONE RECEPTACLE OUTLET THAT IS ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN 6 FEET, 6 INCHES ABOVE GRADE, SHALL BE INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT ACCESS TO GRADE. BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE LOCATED NOT MORE THAN 6 FEET, 6 INCHES ABOVE THE BALCONY, DECK, OR PORCH SURFACE.

6. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED TO SERVE LAUNDRY APPLIANCES.

7. AT LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO ANY PROVIDED FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN EACH BASEMENT AND IN EACH ATTACHED GARAGE, AND IN EACH DETACHED GARAGE OR ACCESSORY BUILDING THAT IS PROVIDED WITH ELECTRICAL POWER. WHERE A PORTION OF THE BASEMENT IS FINISHED INTO ONE OR MORE HABITABLE ROOM(S), EACH SEPARATE UNFINISHED PORTION SHALL HAVE A RECEPTACLE OUTLET INSTALLED IN ACCORDANCE WITH THIS SECTION.

8. HALLWAYS OF 10 FEET OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET. THE HALL LENGTH SHALL BE CONSIDERED THE LENGTH MEASURED ALONG THE CENTERLINE OF THE HALL WITHOUT PASSING THROUGH A DOORWAY.

9. FOYERS THAT ARE NOT PART OF A HALLWAY AND THAT HAVE AN AREA THAT IS GREATER THAN 60 FT2 SHALL HAVE A RECEPTACLE(S) LOCATED IN EACH WALL SPACE THAT IS 3 FEET OR MORE IN WIDTH AND UNBROKEN BY DOORWAYS, FLOOR-TO-CEILING WINDOWS, AND SIMILAR OPENINGS.

10. ALL RECEPTACLES WITHIN A DWELLING SHALL BE TAMPER RESISTANT.

11. BATHROOM CIRCUITING SHALL BE EITHER: A) A 20 AMPERE CIRCUIT DEDICATED TO EACH BATHROOM, OR B) AT LEAST ONE 20 AMPERE CIRCUIT SUPPLYING ONLY BATHROOM RECEPTACLE OUTLETS, PER NEC ARTICLE 210.11(C)3
Electrical LegendE1.1

Read as a table · 636 characters

ELECTRICAL LEGEND
RECESSED CAN LIGHT
SURFACE MOUNTED LIGHT
WALL MOUNTED LIGHT
PENDANT LIGHT
EXHAUST FAN or FAN/LIGHT COMBINATION
CEILING FAN
CEILING FAN/ LIGHT COMBINATION
FLUORESCENT LIGHT
SMOKE DETECTOR CO CARBON MONOXIDE DETECTOR
DUPLEX OUTLET
DUPLEX OUTLET - GROUND FAULT INTERRUPTER
DUPLEX OUTLET - WEATHERPROOF
WALL SWITCH
WALL SWITCH 3-WAY
WALL SWITCH 4-WAY
WALL SWITCH w/ DIMMER

What checks what

The measurement pass never looks at the architect's area table. Where two independent paths land on the same quantity, that is a real check rather than a restatement. The measured footprint runs one to three percent high because the trace follows the outer face of a wall line that has real thickness on paper: a systematic bias, and a correctable one.

Sheets read
9all of them, none skipped
Cited values
143each tied to a box on a sheet
Largest cross-check gap
3.1%on the first floor footprint
QuantityWhat we measuredWhat the set statesDeltaHow
First floor footprint incl. garage3,906 sf3,788 sf+3.1%Traced off the foundation sheet vs. the architect's area table
Second floor footprint956 sf831 sf+15%Measured to outer face; the table is net of the stair opening
Garage and storage1,228 sf1,292 sf−5.0%Room dimension strings vs. area table
Covered rear patio386 sf406 sf−4.9%20'-4″ × 19'-0″ callout
Grilling patio240 sf246 sf−2.4%13'-4″ × 18'-0″ callout
Drawing scale113.6 px/ft112.5 px/ft+1.0%Overall dimension strings vs. the sheet's stated 3/16″ = 1'-0″
Roof pitch8:12 measured8 / 12 printed at the gable peaksmatchLine geometry vs. what is printed on A3.2
Overhead garage doors9'-0″×9'-0″ and 18'-0″×9'-0″same, from the printed calloutmatchTwo independent reads of the same callout

What an estimator should check before pricing

Every one of these is a gap in the drawing set, not a gap in the reading. They are listed so nothing here gets priced as if it were settled.

  • The roofing split. A3.2 specifies asphalt shingle and standing seam metal. The set does not separate the areas, so the 70 square figure covers the whole roof. This is the largest open number here.
  • Roof projection. There is no roof plan in the set. The 2'-0″ overhang is the site plan's own note, and porch roofs are assumed to run at the main 8:12.
  • Gable end area. Siding is quoted at plate height plus a 636 sf gable allowance. The four elevations are in the set and can be measured directly to firm this up.
  • Opening count. Forty-three size callouts were read cleanly. An opening drawn without a printed callout is not in the schedule, so the count is a floor, not a ceiling.
  • Truss count. Trusses are shown as shaded areas on A2.3 rather than laid out individually, so 78 is a spacing calculation. The truss supplier's layout governs.
  • Switches and circuits. Devices are counted; home runs, switch legs and circuit grouping are not. E1.1 itself notes that fixture, switch and outlet locations are all to be verified with the owner.
  • Second floor area. The measured 956 sf encloses the stair opening. Use the architect's 831 sf for anything priced by conditioned area.